Wire gauge and fusing
Current ratings.
Current ratings.
Wire thickness in North America is given as an AWG number (American Wire Gauge), and a smaller number means thicker wire. Thicker wire has less resistance, carries more current and heats less. Two regularities make it easy to remember: every 3 gauges doubles or halves the cross-section area, and every 6 gauges doubles or halves the diameter.
| AWG | Diameter | Area | Resistance (copper) | Building-wire rating |
|---|---|---|---|---|
| 22 | 0.64 mm | 0.33 mm² | 16.1 Ω per 1000 ft | signal wiring only |
| 20 | 0.81 mm | 0.52 mm² | 10.2 Ω per 1000 ft | signal wiring only |
| 18 | 1.02 mm | 0.82 mm² | 6.4 Ω per 1000 ft | light loads only |
| 16 | 1.29 mm | 1.31 mm² | 4.0 Ω per 1000 ft | light loads only |
| 14 | 1.63 mm | 2.08 mm² | 2.5 Ω per 1000 ft | 15 A |
| 12 | 2.05 mm | 3.31 mm² | 1.6 Ω per 1000 ft | 20 A |
| 10 | 2.59 mm | 5.26 mm² | 1.0 Ω per 1000 ft | 30 A |
| 8 | 3.26 mm | 8.37 mm² | 0.63 Ω per 1000 ft | 40 A |
| 6 | 4.12 mm | 13.3 mm² | 0.40 Ω per 1000 ft | 55 A |
Diameters and resistances come from the formula above, for solid copper at 20 °C. The ratings are the conservative figures used for building (mains) wiring. A rating also depends on insulation, bundling and heat, so it is a ceiling for planning rather than a promise. Stranded wire is slightly less conductive than solid for the same gauge.
A fuse or breaker exists to open the circuit before the wire gets hot enough to melt its insulation or start a fire. So size it to the thinnest wire in the circuit: a 20 A breaker needs at least 12 AWG, a 15 A breaker at least 14 AWG. A bigger fuse than the wire rates for lets the wire overheat first.
A 100 W HF radio on 13.8 V can draw 20 A or more when transmitting. Even wire that is rated for the current wastes voltage, and a drop at the radio makes it distort or shut down. Voltage is lost on the way out and back, so the resistance counts twice the length.
At 20 A over a 10 ft run (20 ft of wire in the loop): 14 AWG loses about 1.0 V (7 %), 12 AWG 0.64 V (4.6 %), and 10 AWG 0.40 V (2.9 %). (14 AWG is already past its rating at 20 A.) Use thicker wire, or shorten the run, until the drop is small.